XPD 500 W
XPD 500 W Programmable DC Power Supply
Up to 540 Watts in a Quarter Rack Package
Xantrex Technology Inc.
Headquarters
8999 Nelson Way
Burnaby, British Columbia
Canada V5A 4B5
800 670 0707 Toll Free
604 420 1591 Fax
The Xantrex XPD Series provides more than 500 watts of reliable DC power in a quarter-rack wide
chassis - the highest power density programmable DC power supply available in this power range.
The high power density supplies are ideal for benchtop, ATE systems and OEM applications, where
wide adjustment of output voltage or current is required in a compact package.
For systems applications, the XPD can be rack mounted in multiple-unit configurations of up to four
independent 500 watt outputs. The supplies feature zero voltage or “soft switching” which virtually
eliminates switching transients, and Power Factor Correction (PFC) for low current draw and greatly
reduced generation of input current harmonics.
5916 195th Street NE
Arlington, Washington
USA 98223
800 446 6180 Toll Free
360 925 5144 Fax
Product Features
Zero voltage “Soft Switching”
Power Factor Correction (PFC)
Simultaneous front panel display of output voltage and current
Front and rear connectors
Ten-turn front panel knobs
Remote sense with 5 V line loss compensation
LabVIEW® and LabWindows® drivers
Protection Features
Over voltage protection
Over temperature protection
Options
RS-232 interface card
GPIB interface card
GPIB-multichannel
© 2004 Xantrex Technology Inc. All rights reserved. Xantrex is a trademark of Xantrex International. PN DS20040608R03_xpd500 Printed in Canada
www.xantrex.com
XPD 500 W
XPD 500 W Programmable DC Power Supply
Electrical Specii cations
1
Models
7.5-67 18-30 33-16 60-9 120-4.5
Output Ratings
Output Voltage
2
0-7.5 V 0-18 V 0-33 V 0-60 V 0-120 V
Output Current
3
0-67 A 0-30 A 0-16 A 0-9 A 0-4.5 A
Output Power
502.5 W 540 W 528 W 540 W 540 W
Line Regulation
4
Voltage
2 mV 2 mV 3 mV 3 mV 3 mV
Current
2 mA 2 mA 2 mA 2 mA 2 mA
Load Regulation
5
Voltage
2 mV 4 mV 4 mV 4 mV 5 mV
Current
4 mA 4 mA 4 mA 4 mA 4 mA
Meter Accuracy
Voltage (1% of Vmax + 1 count)
0.2 V 0.3 V 0.5 V 0.7 V 2.2 V
Current (1% of Imax + 1 count)
0.8 A 0.4 A 0.3 A 0.2 A 0.2 A
Output Noise (90-20 MHz)
Voltage (p-p)
45 mV 45 mV 45 mV 45 mV 60 mV
Output Ripple
Voltage
3 mV 3 mV 3 mV 5 mV 10 mV
Current
6
150 mV 50 mV 30 mV 30 mV 15 mV
Drift (60 minutes)
7
Voltage (0.15% of Vmax)
11.3 mV 27 mV 49.5 mV 90 mV 180 mV
Current (0.3% of Imax)
201 mA 90 mA 48 mA 27 mA 13.5 mA
Drift (8 hours)
8
Voltage (0.03% of Vmax)
2.3 mV 5.4 mV 9.9 mV 18 mV 36 mV
Current (0.05% of Imax)
34 mA 15 mA 8 mA 4.5 mA 2.3 mA
Temperature Coefi cient
9
Voltage (0.015% of Vmax/°C)
1.2 mV 2.7 mV 5 mV 9 mV 18 mV
Current (0.02% of Imax/°C)
13.4 mA 6 mA 3.2 mA 1.8 mA 0.9 mA
OVP Adjustment Range(5% to 110% of Vmax)
0.4-8.3 V 0.9-19.8 V 1.7-36.3 V 3-66 V 6-132 V
Efi ciency
110
81% 83% 85% 85% 84%
1. All electrical specii cations are represented at the full operating temperature range for all models, unless otherwise stated.
2. Minimum output voltage is <0.15% of rated voltage at zero output setting.
3. Minimum output current is <0.2% of rated current at zero setting when measured with rated load resistance. Front output current limited to 30 A maximum.
4. For input voltage variation over the AC input voltage range, with constant rated load.
5. For 0-100% load variation, with constant nominal line voltage.
6. Current mode noise is measured from 10% to 100% of rated output voltage, full current.
7. Maximum drift over 60 minutes with constant line, load, and temperature, after power up.
8. Maximum drift over 8 hours with constant line, load, and temperature, after 60 minute warm-up.
9. Change in output per °C change in ambient temperature, with constant line and load.
10. Typical efi ciency at 120 V and full output power.
General Specii cations
Operational AC Input Voltage
84-264 VAC, 47-63 Hz; power factor corrected. Derate maximum output power to 450 W for AC input less than 95 V
Power Factor
0.98 minimum for full load at nominal voltage
Switching Frequency
125 kHz (250 kHz output ripple)
Remote Analog Programming (Full Scale Input)
Voltage and current programming inputs (source must be floating): 0-10 V voltage sources. Input impedance (V and I): 20 k
Remote Programming and Monitoring Accurac
y
Remote Programming and Monitoring Accurac
y
Remote Programming and Monitoring Accurac
1% of full scale output for the default range
Dimensions (HxWxD)
5.2 x 4.2 x 13” (134.7 x 109.2 x 330 mm)
Weight
9.0 lb (4.1 kg)
Warranty
5 years
Approvals
CE-marked units meet; EN61010-1, EN61000-6-2 and EN61000-6-4; CSA C/US certified to UL3111-1 and CSA C22.2 No
1010.1; Meets USA EMC standard: FCC, part 15B, class A; Meets Canadian EMC standard: ICES-001, Class A.
Note: Specii cations are subject to change without notice.